Mechanical Asset Intelligence
Commercial Building Mechanical Report — Quick MAI Report
Report dateOctober 20, 2026Field documentation visit — same day

Roosevelt Industrial Complex

Detroit, MI · Commercial / Light Industrial · Sample building record
74
MAI Overall Score
Fair / Monitor Closely
10
Units Documented
RTUs · boiler · AHU · pumps
2 of 10
Units on R-22
Phased-out refrigerant
$285,000
5-Year Capital Exposure
MAI system calculation
SAMPLE REPORT — Roosevelt Industrial Complex is a fictional building. Data shown is for illustration only.

Building summary

Scores below are MAI's system-calculated values from the building record, shown exactly as computed. Ten pieces of equipment were documented on site on October 20, 2026, with nameplate data extracted from photographs.

71
Mechanical Health
Fair
64
Maintenance Maturity
Developing Documentation / PM
38
Capital Exposure Score
Elevated Capital Exposure
46
Mechanical Risk Score
Moderate-High Risk
Five-year capital exposure (system)
$285,000

MAI's modeled exposure for this building over the next five years. Per-unit Detroit-metro replacement estimates are in the capital planning section: the sequenced work — two R-22 rooftop replacements, a boiler replacement, an air-handler refurbishment, and one pump — spans $229,000–$351,000 at today's local prices, deliberately sequenced across budget years.

Expected service exposure (system)
$21,500

System-calculated expected service spend over the same five-year window, driven by the age of the two R-22 units and the boiler's original burner.

Total replacement exposure (system)
$612,000

Modeled cost of replacing every documented unit at end of life at today's Detroit-metro prices — the long-horizon figure the five-year plan is sequenced against.

The headline story: this building's roof and boiler room carry two generations of equipment. Two packaged rooftop units run on phased-out R-22 — one at 22 years old, one at 18 — and the 2012 boiler is showing section wear with its original burner. The other six units are modern R-410A equipment in fair-to-good condition and need nothing but documented preventive maintenance. The plan below sequences the end-of-life work across five budget years so no single year carries the whole $285,000.

Unit by unit

Nameplate data was read from photographs taken on site. Anything the plate didn't state — or that couldn't be read — is marked as such rather than filled in. Manufacture years decoded from serial numbers are marked "verify."

RTU 1 — Carrier packaged rooftop unit

Unit 01 · Main roof, east · Serves: Warehouse A · Status: Operating
Replace — plan now · 22 yrs · R-22
Nameplate data
ManufacturerCarrier (WeatherMaster)
Model48TCD28B3A0A0A0
Serial3404G51208
Manufacture year2004 (decoded from serial — verify)
Age~22 years
RefrigerantR-22 · factory charge 38 lb
 
Cooling capacity240,000 BTUH · 20 tons
Heating input400,000 BTUH · Natural gas
Electrical460V · 3 phase
MCA / MOCP54 / 70
Read confidence88 / 100
Service & PM details
Filters20×25×2 pleated (MERV 8) · qty 8
BeltBX78 · qty 2 (matched set)
PM cadenceFilters quarterly · belts checked semi-annually
Recommendation — begin replacement planning now At ~22 years old on phased-out R-22, this unit is past typical packaged-unit service life. R-22 production ended in 2020; every recharge and compressor part gets scarcer and pricier, and a mid-summer failure over Warehouse A becomes an emergency changeout at emergency prices. Get replacement quotes this budget cycle. Planning estimate for a like-for-like 20-ton packaged RTU replacement (Detroit metro, installed): $40,000–$65,000.

RTU 2 — Trane packaged rooftop unit

Unit 02 · Main roof, west · Serves: Warehouse B · Status: Operating
Budget replacement · 18 yrs · R-22
Nameplate data
ManufacturerTrane (Precedent)
ModelTCH300E3E0A0A
Serial82204917L
Manufacture year2008 (decoded from serial — verify)
Age~18 years
RefrigerantR-22 · factory charge 44 lb
 
Cooling capacity300,000 BTUH · 25 tons
Heating input500,000 BTUH · Natural gas
Electrical460V · 3 phase
MCA / MOCP68 / 90
Read confidence91 / 100
Service & PM details
Filters20×20×2 pleated (MERV 8) · qty 12
BeltBX85 · qty 2 (matched set)
PM cadenceFilters quarterly · belts checked semi-annually
Recommendation — budget replacement in years 1–3 At 18 years on R-22, this unit doesn't need replacing today, but it belongs in the capital budget now, sequenced after RTU 1 so the two biggest changeouts don't land in the same year. Planning estimate (Detroit metro, installed): $51,000–$81,000.

RTU 3 — York packaged rooftop unit

Unit 03 · Office roof · Serves: Front offices · Status: Operating
Verify at next visit · Age unknown
Nameplate data
ManufacturerYork (cabinet branding)
ModelNot readable — plate sun-bleached
SerialNot readable — plate sun-bleached
Manufacture yearNot readable
AgeUnknown — cannot be determined from this plate
RefrigerantNot determinable from plate — verify on site
 
Cooling capacityNot stated / not readable — size class ~15 tons from cabinet footprint (verify)
Heating inputNot readable
Electrical460V disconnect at unit · 3 phase
MCA / MOCPNot readable
Read confidence41 / 100 — human review flagged
Service & PM details
FiltersNot recorded — plate unreadable; record size & quantity at next service visit
BeltNot recorded — verify at next service visit
PM cadenceSet once filter and belt sizes are documented
Recommendation — verify and document at the next service visit This is the one unknown on the roof. With the plate bleached, its age, refrigerant, and capacity — and therefore its place in the replacement queue — can't be set yet. At the next visit: check the compressor tags and blower-section labels, look for the serial on the inside of the electrical panel door, and record refrigerant type from the compressor plate. If it proves to be a similar vintage to RTU 1 and RTU 2, it joins the plan; the contingent planning range, if replacement becomes necessary, is $30,000–$48,000 (~15-ton class, Detroit metro, installed, pending verification).

RTU 4 — Carrier packaged rooftop unit

Unit 04 · Main roof, center · Serves: Warehouse C · Status: Operating
No action — monitor · 7 yrs · R-410A
Nameplate data
ManufacturerCarrier (WeatherExpert)
Model48TC*14N3A0A0A0
Serial2319G88412
Manufacture year2019 (decoded from serial — verify)
Age~7 years
RefrigerantR-410A · factory charge 19 lb
 
Cooling capacity120,000 BTUH · 10 tons
Heating input224,000 BTUH · Natural gas
Electrical460V · 3 phase
MCA / MOCP29 / 40
Read confidence94 / 100
Service & PM details
Filters20×25×2 pleated (MERV 8) · qty 4
BeltBX58 · qty 1
PM cadenceFilters quarterly · belt checked semi-annually
Recommendation — no action; routine preventive maintenance Modern refrigerant, mid-life, clean read. Keep it on a documented PM schedule — filters, belts, coil cleaning, drain checks, economizer test — and it stays out of the capital plan well beyond this report's five-year window.

RTU 5 — Trane packaged rooftop unit

Unit 05 · Main roof, south · Serves: Shipping / staging · Status: Operating
No action — monitor · 9 yrs · R-410A
Nameplate data
ManufacturerTrane (Precedent)
ModelYCH240E3L0A0A
Serial171104482L
Manufacture year2017 (decoded from serial — verify)
Age~9 years
RefrigerantR-410A · factory charge 33 lb
 
Cooling capacity240,000 BTUH · 20 tons
Heating input400,000 BTUH · Natural gas
Electrical460V · 3 phase
MCA / MOCP51 / 70
Read confidence92 / 100
Service & PM details
Filters16×25×2 pleated (MERV 8) · qty 8
BeltBX66 · qty 2 (matched set)
PM cadenceFilters quarterly · belts checked semi-annually
Recommendation — no action; routine preventive maintenance The largest modern unit on the roof and in good documented condition. PM only — filters, belts, coils, drains, economizer test — with a mid-life compressor and controls check around year 12.

RTU 6 — Lennox packaged rooftop unit

Unit 06 · Office roof · Serves: Office mezzanine · Status: Operating
No action — monitor · 5 yrs · R-410A
Nameplate data
ManufacturerLennox (KCA)
ModelKCA180S4BN1G
Serial5621K04417
Manufacture year2021 (decoded from serial — verify)
Age~5 years
RefrigerantR-410A · factory charge 26 lb
 
Cooling capacity180,000 BTUH · 15 tons
Heating input300,000 BTUH · Natural gas
Electrical460V · 3 phase
MCA / MOCP41 / 60
Read confidence95 / 100
Service & PM details
Filters20×25×2 pleated (MERV 8) · qty 6
BeltDirect drive — no belt
PM cadenceFilters quarterly · fan and motor check semi-annually
Recommendation — no action; routine preventive maintenance The newest rooftop unit in the building. Routine PM only; no capital exposure inside the five-year window.

BLR 1 — Weil-McLain sectional boiler

Unit 07 · Boiler room · Serves: Building heating loop · Status: Operating
Budget replacement · 14 yrs · Sections weeping
Nameplate data
ManufacturerWeil-McLain (LGB)
ModelLGB-15
SerialCP 6620412
Manufacture year2012 (from rating plate)
Age~14 years
FuelNatural gas · atmospheric burner (original)
 
Heating input1,500,000 BTUH
Net output (I=B=R)~1,140,000 BTUH
Electrical120V controls
Condition notesTwo sections weeping at push nipples; burner original and parts-limited
Read confidence90 / 100
Service & PM details
Filtersn/a — gas-fired; no air filters
Burner serviceBurner orifices & gas strainer cleaned at annual PM · flame rod and igniter inspected
PM cadenceAnnual combustion analysis & safety-control testing — see Inspections & compliance below
Recommendation — budget replacement in years 3–5; annual combustion service now A cast-iron sectional boiler can outlive this one — but two weeping sections plus an original, parts-limited burner move it into the plan. Keep annual combustion analysis and safety-control testing on the calendar, and budget a like-for-like replacement in years 3–5 while the changeout can still be scheduled in shoulder season. Planning estimate (Detroit metro, installed, including rigging and flue reconnection): $88,000–$125,000.

AHU 1 — Trane air handler

Unit 08 · Penthouse · Serves: Office floors (with RTU 3 / RTU 6 zones) · Status: Operating
Refurbish · 12 yrs · R-410A DX coil
Nameplate data
ManufacturerTrane (Climate Changer)
ModelCSAA025UAL00
SerialK14F22108
Manufacture year2014 (decoded from serial — verify)
Age~12 years
RefrigerantR-410A (DX cooling coil)
 
Airflow25,000 CFM class
Motor25 HP · 460V · 3 phase · belt drive
Condition notesBearing play at supply fan; coil fin damage on two rows; belts at wear limit
MCA / MOCP38 / 50
Read confidence89 / 100
Service & PM details
Filters24×24×2 pleated prefilter · qty 6 — plus 24×24×12 rigid-cell final filters · qty 6
BeltBX105 · qty 3 (matched set) — at wear limit; replace at refurbishment
PM cadencePrefilters quarterly · final filters annually · belts checked semi-annually
Recommendation — refurbish in years 2–4, don't replace The cabinet and coils have years left; the wear is in the rotating parts. Budget a refurbishment — supply-fan bearings and shaft inspection, belts and sheaves, coil fin comb-out and cleaning, drain pan treatment — in years 2–4. Planning estimate (Detroit metro): $16,000–$26,000. Full replacement is beyond the five-year window.

P-1 — Bell & Gossett heating-water pump

Unit 09 · Boiler room · Serves: Main heating loop · Status: Operating
No action — monitor · 8 yrs
Nameplate data
ManufacturerBell & Gossett (Series 1510)
Model1510 4GB · 15 HP
SerialD1844107
Manufacture year2018 (from motor plate)
Age~8 years
DutyHeating water · 450 GPM @ 60 ft head
 
Motor15 HP · 460V · 3 phase · 1760 RPM
Condition notesSeal dry, coupling aligned at last PM, no bearing noise
ElectricalMCA per disconnect label 21 / 30
Read confidence93 / 100
Service & PM details
Filters / beltsNone — close-coupled pump, direct drive
PM cadenceMechanical seal and bearing check semi-annually · coupling guard inspected at each visit
Recommendation — no action; routine preventive maintenance Mid-life and clean at inspection. Seal and bearing checks on the normal PM route; no capital exposure inside the five-year window.

P-2 — Taco condensate / booster pump

Unit 10 · Boiler room · Serves: Condensate return · Status: Operating — worn
Budget replacement · 17 yrs · Seal leaking
Nameplate data
ManufacturerTaco (Series 1600)
Model1632D3E1 · 3 HP
Serial09-44817
Manufacture year2009 (decoded from serial — verify)
Age~17 years
DutyCondensate return · 90 GPM @ 40 ft head
 
Motor3 HP · 460V · 3 phase · 3450 RPM
Condition notesMechanical seal weeping; mineral scale at volute; amp draw above plate at load
ElectricalMCA per disconnect label 6 / 15
Read confidence86 / 100
Service & PM details
Filters / beltsNone — close-coupled pump, direct drive
PM cadenceSeal weep monitored monthly until the scheduled replacement (years 1–3)
Recommendation — budget replacement in years 1–3 Small money, outsized nuisance: a condensate pump failure takes the heating loop down with it. At 17 years with a weeping seal and high amp draw, replace on schedule rather than on a breakdown. Planning estimate (Detroit metro, installed): $4,000–$6,000.

Inspections & compliance

Boiler inspection certificates and safety-control test results on file for BLR 1 (Weil-McLain LGB-15, boiler room) — stored in the building's permanent record, not in a binder in the boiler room.

Boiler inspections — BLR 1

InspectionPerformed byCertificate / referenceLast inspectionNext dueStatus
State boiler inspectionState of Michigan — Boiler DivisionCertificate MI-B-2026-0417March 12, 2026March 2027Current
Insurance inspectionHartford Steam Boiler Inspection & Insurance Co.Report HSB-88-22140March 12, 2026 (joint visit)March 2027Current

CSD-1 controls & safety devices test — BLR 1

ASME CSD-1 periodic testing of the boiler's controls and safety devices, performed with the annual combustion service on September 18, 2026.

ComponentWhat was testedResultTest date
Operating controlCut-out / cut-in at setpointPassSeptember 18, 2026
High-limit controlManual-reset high limit trips and locks outPassSeptember 18, 2026
Low-water cutoffBlowdown test — burner shuts down on low waterPassSeptember 18, 2026
Safety relief valveTry-lever test; set pressure 30 psi verified against platePassSeptember 18, 2026
Flame safeguardFlame failure response and pilot turndown testPassSeptember 18, 2026
The paperwork lives with the building Filter and belt sizes, inspection certificates, and CSD-1 results live in the building's permanent record — so the next technician arrives with the right parts already on the truck, and the paperwork is audit-ready when the state or the insurer asks for it.

Capital planning — five-year outlook

Sequenced by urgency so the two end-of-life R-22 units and the boiler don't land in the same budget year. Every figure is a planning estimate localized to this building's own market — Detroit metro — not a national average and not a quote; actual pricing depends on verified capacity, curb and crane requirements, and contractor bids. See "How these estimates are built" below the table.

WindowUnitActionPlanning estimate
Now – Year 1RTU 1 (Carrier, 2004)Replacement planning — obtain quotes this budget cycle$40,000–$65,000
Now – Year 1RTU 3 (York, year unknown)Documentation only — recover serial/year/refrigerant from compressor and panel labels at next service visitService visit only
Years 1–3RTU 2 (Trane, 2008)Budgeted replacement — planned changeout after RTU 1$51,000–$81,000
Years 1–3P-2 (Taco, 2009)Budgeted replacement — scheduled pump changeout$4,000–$6,000
Years 2–4AHU 1 (Trane, 2014)Refurbishment — bearings, belts/sheaves, coil restoration, drain treatment$16,000–$26,000
Years 3–5BLR 1 (Weil-McLain, 2012)Budgeted replacement — shoulder-season changeout; annual combustion service until then$88,000–$125,000
ContingentRTU 3 (York)Joins the replacement queue if verification shows comparable age; otherwise monitor$30,000–$48,000 if needed
OngoingRTU 4 · RTU 5 · RTU 6 · P-1Routine PM only; replacements beyond the five-year windowPM costs only

How the per-unit ranges relate to the system's headline figure: MAI's system-calculated five-year capital exposure for this building is $285,000 — a modeled exposure figure, not a quote and not a simple sum of the rows above. Adding the sequenced rows (RTU 1 at $40,000–$65,000, RTU 2 at $51,000–$81,000, the boiler at $88,000–$125,000, AHU 1 refurbishment at $16,000–$26,000, and P-2 at $4,000–$6,000) spans $199,000–$303,000, and $229,000–$351,000 with contingent RTU 3 included; the modeled $285,000 sits inside that combined span. The two numbers measure different things — modeled five-year exposure vs. the cost of doing every sequenced job outright at today's Detroit-metro prices — and the plan deliberately sequences the work into different budget years so no single year carries all of it.

How these estimates are built These estimates are localized to the building's own market — Detroit, MI — because installed mechanical prices follow local labor and market conditions; the same unit carries a different price in a different market. The basis: published 2025–2026 installed-cost benchmarks for packaged rooftop units (roughly $2,000–$3,200 per ton in the 3–5 ton class, including curb adapter, gas and electrical reconnection, and disposal; crane work, where required, is extra; larger packaged units are priced from the same benchmark family per ton), adjusted by the RSMeans City Cost Index location factor for Detroit mechanical work: index 100.9 against a national average of 100 — a factor of about 1.01, so Detroit-metro mechanical pricing sits essentially at the national average. (For contrast, Miami's mechanical index in the same RSMeans table is 84.8 — roughly 15% below the national average — which is why estimates are always built for the building's own market.) Boiler and pump figures use the same method against published installed-cost benchmarks for commercial hot-water boilers and end-suction pumps in the Detroit market. Where a nameplate states capacity, the estimate uses it; where it does not (RTU 3), the size class is taken from the cabinet footprint and the figure is marked pending verification. Estimates prepared October 2026. They are planning figures, not quotes: actual pricing varies with verified capacity, installation conditions, equipment tier, and contractor bids.

Priority actions

  1. Start RTU 1 replacement planning now. 22 years old, R-22, past typical service life. Get quotes this budget cycle while it's still a planned purchase, not an emergency.
  2. Put RTU 2 in the capital budget for years 1–3. 18 years old, R-22 — a planned replacement, sequenced after RTU 1.
  3. Re-document RTU 3 at the next service visit. Serial, year, and refrigerant are unreadable (sun-bleached plate). Check compressor tags and the inside of the electrical panel door so its age and place in the queue can be set.
  4. Budget the boiler for years 3–5, and keep annual combustion service until then. Two sections are weeping and the burner is original — replace on a shoulder-season schedule, not on a January failure.
  5. Refurbish AHU 1 in years 2–4 and replace P-2 in years 1–3. Bearings, belts, and coil work on the air handler; a scheduled changeout for the small condensate pump before its leaking seal takes the heating loop down.
  6. Verify the serial-decoded years (RTU 1: 2004, RTU 2: 2008, RTU 4: 2019, RTU 5: 2017, RTU 6: 2021, AHU 1: 2014, P-2: 2009) against unit records at the next visit.
  7. Stand up a documented PM program. Maintenance maturity scores 64 — "Developing." Regular documented PM on all ten units is what protects the six good units and stretches the aging ones safely.
  8. Leave RTU 4, RTU 5, RTU 6, and P-1 alone beyond PM. Modern refrigerant, fair-to-good condition — no action needed.

About this report

This is a sample report. Roosevelt Industrial Complex is a fictional building, and every name, value, and figure on this page was created for illustration. A real MAI report is a planning snapshot built from a field documentation visit — equipment photographs and nameplate data, with AI-assisted extraction (per-read confidence scores shown per unit). It is not an engineering inspection, a condition assessment by a licensed engineer, or a quote. Manufacture years decoded from serial numbers are marked "verify." Cost figures are planning ranges localized to the building's own market — built from published national installed-cost benchmarks adjusted by the RSMeans location factor for that market, as detailed under "How these estimates are built" — and will vary with verified capacity, installation conditions, and contractor bids. Scores are MAI system-calculated values from the building record as of the report date.